Ability of destruction in weight: 60 Kg/h.

It should be in a position to operate not less than 10 hours/day

This incinerator must be able to destruct all combustible wastes generated by hospitals, private clinics, labs, institutes, etc…

Design Specification: Forms A, B, C, D, and E of medical waste 

“PYROLYTIC” combustion, by simply controlling the gasification of waste.

The incinerator must prevent the discharge of smoke and fine dust, (Smokeless) throughout the loadings.

It should be able to decrease the volume of wastes from 98%.

It should be in a position to hold emission in the next burn with gas residence of not less than 2 seconds.

The incineration must be completely free of visible smoke in addition to offensive odours.

The reduced volt electricity (L.C.P) of this waste will be 3,500 kcal/kg

The Temperatures of combustion: Minimum will be 850oC and maximum 1400oC

Post combustion: 1100oC.

The Internal diameter of the Chimney: Ø 400 and its elevation: 8 m

The Loudness of the combustion room: 1.200 L

The Dimension of this door for loading in cm: 70×70.

Burner operation should be Automatic On/Off

Gas: petrol

The supplier must provide  necessary information for the top of  this installment

This incinerator with”PYROLYTIC” combustion must have:

A combustion chamber of waste:

* Totally tight door for your manual loading of waste.  The loading must be Manual, Batch Load 

* A burner of light which the usage is limited to the ignition of waste.

* Frontage of loading door seals gone on hinges, wheel of screw plug, elastic joint, and stuffing insulating from refractory.

* The insulating material of the combustion chamber should be composed of refractory bricks, so using a high content of aluminum and insulates bricks so as to assure a minimum temperature on   the exterior sheet metal. Thickness : ≥100 mm

. Nature: 42% of Al203

Insulate in fibrous panels:

. Thickness: ≥75 mm

Nature: Calcium silicate.

* Burner of light of waste, together with gas, regular mono-bloc casting directing stirring flame, lighting and safety of digital ignition, permanent venting, electromagnetic sluice gate of regulation and isolating valve.

. Thickness: ≥75 mm

Nature: Calcium silicate.

* Burner of lighting of waste, with fuel, standard mono-bloc casting guiding  plunging flame, lighting and safety of electronic ignition, permanent ventilation, electromagnetic sluice gate of regulation and isolating valve.

* Plate of combustion in Carborundum, avoiding the fixing of glass and slags.